Guidelines for Grounding Maintenance and Electric Shock Risk Prevention of Electroplating Equipment
The electroplating industry has a humid and highly corrosive production environment, and equipment often involves high voltage and high current operations. The reliability of the grounding system is directly related to personnel safety and equipment stability. Proper grounding maintenance is the core aspect of safety management for electroplating manufacturers. The following analysis focuses on grounding system requirements, daily maintenance points, common problem solutions, and comprehensive preventive measures.
1、 Core requirements for grounding system of electroplating equipment
1. Clearly define the type of grounding
-Protective grounding: For equipment casings, metal frames, operation consoles, etc., it is a line of defense for personnel safety to prevent the casing from being electrified in case of leakage.
-Working grounding: Provide reference potential for the normal operation of electroplating power supply, rectifier and other equipment, and strictly follow the requirements of the equipment manual.
-Repeated grounding: Multiple grounding points are applied to the neutral wire (such as workshop entrances and equipment concentration areas) to avoid protection failure in case of neutral wire breakage and enhance system reliability.
2. Grounding resistance standard
-Protective grounding resistance ≤ 4 Ω; Repeated grounding resistance ≤ 10 Ω; The working grounding resistance needs to be adjusted according to the characteristics of the equipment (such as rectifier grounding usually ≤ 1 Ω).
-The grounding resistance needs to be regularly tested to ensure compliance with national standards (GB 50169-2016 "Code for Construction and Acceptance of Grounding Devices").
3. Material selection
Priority should be given to using corrosion-resistant materials: galvanized flat steel (thickness ≥ 4mm), copper bars (cross-sectional area ≥ 25mm ²), or stainless steel grounding bodies to avoid grounding failure caused by acid and alkali corrosion of ordinary carbon steel. Tin plated or galvanized bolts should be used at the connection points to reduce contact resistance.
2、 Key steps for daily grounding maintenance
1. Regularly check the connection points
-Frequency: At least once a month, focus on checking whether the bolts are loose and whether the contact surfaces are corroded/oxidized (especially in areas with high concentrations of acid and alkali mist).
-Solution: After removing the oxide layer, apply conductive paste, re tighten and use anti loosening nuts/spring washers to prevent loosening caused by vibration.
2. Grounding resistance detection
-Tool: Use a professional grounding resistance tester (such as ZC-8 type), disconnect the power supply of the equipment during testing to ensure accurate data.
-Frequency: Once every quarter, with an increase in testing frequency during rainy season or after equipment renovation.
3. Grounding inspection of mobile devices
-Mobile equipment such as cranes and electric hoists: Check whether the connection between the track and the grounding body is firm, and whether the sliding contact wire grounding is effective.
-Hanger and cathode rod: Ensure good contact to avoid the risk of local heating or electric shock caused by poor contact.
4. Confirmation of grounding of auxiliary equipment
The grounding terminals of auxiliary equipment such as circulation pumps, heating pipes, and fans need to be checked one by one and cannot be missed; Temporary equipment (such as temporary power supply) must use dedicated grounding clamps, and it is prohibited to use metal pipes instead of grounding bodies.
3、 Common grounding issues and solutions
1. Corrosion of grounding body
-Phenomenon: Large areas of rust appear on the surface of the grounding body, and the resistance value exceeds the standard.
-Solution: Replace with stainless steel or tin plated copper bars, bury the grounding body at a depth of ≥ 0.8 meters (away from the acid-base pool), and apply anti-corrosion conductive paint on the surface.
2. Poor contact at the connection point
-Phenomenon: Contact point heating, increased resistance, and even sparking.
-Solution: Polish the contact surface to a metallic luster, apply conductive paste, and then re tighten it; Adopting double bolt fixation to enhance stability.
3. Grounding system failure
-Phenomenon: The equipment casing is electrified, and the leakage protector frequently trips.
-Solution: Conduct a comprehensive investigation of the grounding grid layout to ensure that the connection path between the grounding body and the equipment is uninterrupted; If the grounding grid is aging, it needs to be redesigned and laid again.
4、 Comprehensive prevention of electric shock risk
1. Leakage protector configuration
-All equipment circuits must be equipped with leakage protectors (operating current ≤ 30mA, operating time ≤ 0.1s), and the tripping function must be tested monthly.
-Waterproof leakage protectors should be used in damp areas (such as around plating tanks).
2. Personnel operation standards
-Operators must wear insulated shoes and gloves, and are prohibited from operating equipment with wet hands or touching live parts.
-Regularly conduct safety training to popularize grounding knowledge and first aid skills for electric shock.
3. Equipment insulation testing
-Every six months, use a megohmmeter to test the insulation resistance of equipment (insulation resistance of motors, cables, etc. ≥ 0.5M Ω), and replace aging components in a timely manner.
4. Environmental management
-Keep the workshop floor dry and install a drainage system to prevent electrolyte accumulation; Regularly clean acid and alkali mist to reduce corrosion to the grounding system.
Conclusion
Grounding maintenance is a fundamental project for the safety of electroplating production, and it is necessary to establish a normalized management system to incorporate inspection, testing, and maintenance into daily work processes. Only by continuously paying attention to the reliability of the grounding system can we fundamentally prevent electric shock accidents and ensure the safety of personnel and stable operation of equipment.